Key Features
- 48V DC or 230V AC input; 230V, 50 Hz output (hardwired)
- 10KWcontinuous output, 30000 watts peak output
- Microprocessor controlled Smart UPS & Solar operational mode
- 4-Step Progressive Charging & 7-Battery Type Selector
- Fully compatible for Solar/Wind solutions for Hybrid configuration
- Pure sine wave output with LCD display
- High Efficiency Using Line-Interactive Circuit Topology(Full Bridge Topology)
- Quiet, high efficiency operation, high surge capacity and low idle current
Specifications
INPUT SPECIFICATION
| Input Phase & Wave Form | Single Phase & Sine wave (Utility or Generator) |
| Nominal Voltage | 220/230/240V AC |
| Input AC voltage Window | 154-273C AC |
| Line Low Transfer | 154V +/- 4% |
| Low Voltage Re engage | 164V +/- 4% |
| High Voltage Trip | 273V +/- 4% |
| High Voltage Re engage | 263V +/- 4% |
| Max Input AC Voltage | 270V |
| Nominal Input Frequency | 50Hz or 60Hz (Auto detect) |
| Low frequency trip | 40Hz |
| High frequency trip | 80Hz |
| Output Connection type | Hardwire via built in junction box with cover plate |
INVERTER OUTPUT SPECIFICATION
| Output Wave form & Phase | Pure Sine wave & Single Phase (Bypass mode sync to Input) |
| Power Factor | 1 |
| Nominal Output Voltage RMS | 220/230/240V AC (L-N) (same as input on Bypass mode) |
| Output Voltage regulation | +/-10% RMS (bypass mode sync to input) |
| Output frequency | 50Hz +/-0.3Hz or 60Hz+/-0.3Hz |
| Nominal Efficiency | >88% |
| Output Connection type | Hardwire via built in junction box with cover plate |
| Surge rating/crest factor | 3 times of rating |
| Output continuous power in Watts | 10000 |
| Output continuous power in VA | 10000 |
| Short circuit protection | Yes, fault after 10sec |
DC INPUT SPECIFICATION
| Nominal Input Voltage Dc | 48V DC |
| Minimum start voltage Dc | 40V DC |
| Low battery Alarm | 44V DC |
| Low battery trip | 40V DC |
| High Voltage alarm | 64V DC |
| Over Charge Voltage | 62.8V DC |
| Max Charging Current | 85A DC |
| DC Connection type | DC INPUT: Set of 2 DC bolt-down terminals. AC INPUT: Hardwire via built in junction box with cover plate |
TRANSFER EFFICIENCY
| Transfer Time | 6-10mSec |
| Line Mode | >95% |
| Battery Model | >85% |
| Power Save | Available when the load is less than 75W |





Reviews