Key Features
- 48V DC or 230V AC input; 230V, 50 Hz output (hardwired)
- 6000 watts continuous output, 12000 watts peak output
- Microprocessor controlled Smart UPS & Solar operational mode
- 4-Step Progressive Charging & 7-Battery Type Selector
- Fully compatible for Solar/Wind solutions for Hybrid configuration
- Pure sine wave output with large LCD display
- High Efficiency Using Line-Interactive Circuit Topology(Full Bridge Topology)
- Quiet, high efficiency operation, high surge capacity and low idle current
- CE Safety
Specifications
INPUT AC
| Input Wave Form | Sine wave (Utility or Generator) |
| Nominal Voltage | 230V AC |
| Low Voltage Trip | 154V +/- 4% |
| Low Voltage Re engage | 164V +/- 4% |
| High Voltage Trip | 253V +/- 4% |
| High Voltage Re engage | 243V +/- 4% |
| Max Input AC Voltage | 270V |
| Nominal Input Frequency | 50Hz or 60Hz (Auto detect) |
| Low frequency trip | 47Hz for 50Hz, 57Hz for 60Hz |
| High frequency trip | 55Hz for 50Hz, 65Hz for 60Hz |
| Output Wave form(bypass mode) | Same as Input |
| Overload protection | Circuit breaker |
| Short circuit protection | Circuit breaker |
| Efficiency on line transfer mode | 95% |
| Line transfer time | 10 mSec Typical |
| Bypass without Battery connected | Yes |
| Max bypass current | 45Amp |
INVERTER SPECIFICATION/ OUTPUT
| Output Wave form | Pure Sine wave |
| Output continuous power in Watts | 6000 |
| Output continuous power in VA | 6000 |
| Power Factor | 1 |
| Nominal Output Voltage RMS | 230V AC (L-N) |
| Output Voltage regulation | +/-10% rms |
| Output frequency | 50Hz +/-0.3Hz or 60Hz+/-0.3Hz |
| Nominal Efficiency | >88% |
| Surge rating | 18000 |
| Short circuit protection | Yes, fault after 10sec |
INVERTER SPECIFICATION/ INPUT
| Nominal Input Voltage Dc | 48V |
| Minimum start voltage Dc | 40V |
| Low battery Alarm | 42V |
| Low battery trip | 40V |
| High Voltage alarm | 64V |
| Power Saver | Below 25Watts when enabled |
| Power Saver | Same switched On/Off remote |
| Input connection type | Terminal block with secure enclosure |
CHARGER MODE SPECIFICATION
| AC input Voltage Range | 164-253V AC |
| Output Voltage (DC) | Depends on battery type |
| Battery Charge current | 50Amp |
| Battery initial Voltage for start up | 0-62.8V DC |
| Over charge protection shutdown | 62.8V DC |
| Battery Type (Boost Voltage) | 14.00 |
| Gel USA (Boost Voltage) | 14.10 |
| AGM.1 (Boost Voltage) | 14.60 |
| AGM.2 (Boost Voltage) | 14.40 |
| Sealed Lead acid (Boost Voltage) | 14.40 |
| Gel Euro (Boost Voltage) | 14.80 |
| Open Lead acid (Boost Voltage) | 15.10 |
| Gel USA (Float Voltage) | 13.70 |
| AGM.1 (Float Voltage) | 13.40 |
| AGM.2 (Float Voltage) | 13.70 |
| Sealed Lead acid (Float Voltage) | 13.60 |
| Gel Euro (Float Voltage) | 13.80 |
| Open Lead acid (Float Voltage) | 13.30 |
| Calcium (Float Voltage) | 13.60 |
| De-sulphation | 15.5 for 4hrs (per battery) |
| Remote control/RS232/USB | Yes. Optional |
| Size (in mm) | 218x117x600 |
| Weight | 44kgs |
| Warranty | 2 Year limited warranty Extendable up to 4 years |
| Safety | EMC/CE/ROHS/ISO9001 |
CERTIFICATION / CONFORMITY
| Disturbance at Mains Terminals | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
| Radiated Disturbance | EN61000-6-3:2007+ A1: 2011+ AC:2012 |
| Harmonic Current Emission | EN61000-3-12: 2011 |
| Voltage fluctuations & flickering | EN61000-3-11: 2000 |
| Electrostatic Discharge (ESD) | IEC 6100-4-2:2008 |
| Radio-frequency & continues radiated disturbances | IEC 6100-4-3:2006 + A1:2007 + A2:2010 |
| EFT/B Immunity | IEC 6100-4-4:2012 |
| Surge immunity | IEC 6100-4-5:2014 |
| Conducted RF immunity | IEC 6100-4-6:2013 |
| Power frequency magnetic field | IEC 6100-4-8:2009 |
| Voltage DIP | >95% reduction,IEC 6100-4-11:2004 |
| Voltage DIP | >30% reduction,IEC 6100-4-11:2004 |
| Voltage Interruption | IEC 6100-4-11:2004 |






Reviews